Form RZ-NA O-MAPS II, P/N 209179 R7, Page 1
FORM O-MAPS II (Version B)
Obsoletes Form O-MAPS II (Version A)
Applies to: MAPS II Model Series RCA, RDA,
RDCA, RDDA, RECA, and REDA
Modular Air Processing Systems
MAPS
®
II Model RDCA

Operation/Maintenance/Service
WARNING:
All systems contain chlorodiuoromethane (HCFC-22) or a hydro-uorocarbon
blend (HFC-407C). HCFC-22 is believed to harm the public health and environment
by destroying ozone in the upper atmosphere. Do not release HCFC-22 to
the atmosphere. The U.S. Clean Air Act requires the recovery of any residual
refrigerant.
IMPORTANT: Do not release refrigerant to the atmosphere! If required service
procedures include the adding or removing of refrigerant, the service technician
must comply with all federal, state and local laws. The procedures discussed in
this manual should only be performed by a qualied HVAC technician.
WARNING:
Improper installation, adjustment, alteration, service, or maintenance can cause
property damage, injury, or death. Read the installation, operation, and maintenance
®
®
Seitenansicht 0
1 2 3 4 5 6 ... 27 28

Inhaltsverzeichnis

Seite 1 - II Model RDCA

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 1�FORM O-MAPS II (Version B) Obsoletes Form O-MAPS II (Version A) Applies to: MAPS II Model Series RCA, RDA

Seite 2 - Contents

Form O-MAPS II, P/N 209179 R7, Page 10Re-Heat Pump Reheat Cycle PerformanceFIGURE 4B - Operating Discharge Head Pressure vs Outdoor Ambient Temperatur

Seite 3 - Intensity Levels used

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 11The re-heat heat pump refrigerant circuit is a closed system that includes the same components as the larg

Seite 4 - Requirements

Form O-MAPS II, P/N 209179 R7, Page 12HandlingCompressor Maintenance Checklist, Steps 1-13 NOTE: Compressors for RDCA and RECA are the same as for M

Seite 5 - Controls and Service Ports

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 13RCA RDA Compressor P/N's by Refrigerant, Location, and Voltage - See FIGURE 7.Compressor Location A

Seite 6 - 3.0 Filters

Form O-MAPS II, P/N 209179 R7, Page 14Oil Charge in R22 Compressors used on MAPS II Units CAUTION: POE oil used with R407C refrigerant is irri-tating

Seite 7 - Components

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 15Step 5. Braze on Suction and Discharge Lines Flow an inert gas, such as nitrogen (N2), through the syste

Seite 8 - 5.0 Coil

Form O-MAPS II, P/N 209179 R7, Page 16FIGURE 9 - Pressure Rise vs TimeIMPORTANT NOTE: Always check gauge hose connections for leaks prior to evacuatio

Seite 9

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 17

Seite 10 - (cont'd)

Form O-MAPS II, P/N 209179 R7, Page 18 Step 10. System StartupAssure voltage to compressor does not drop below minimum allowable voltage (eg. 187 vol

Seite 11 - Replacement

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 19tension counterclockwise until the spring tension is relieved. Count and record the number of turns requir

Seite 12

Form O-MAPS II, P/N 209179 R7, Page 21.0 GENERALThis booklet includes operation, maintenance, and service information. Before beginning any procedur

Seite 13

Form O-MAPS II, P/N 209179 R7, Page 209.0 Gas Heat Section Maintenance - Models RDCA and RDDAThis gas heater will operate with a minimum of maintenan

Seite 14

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 21Gas-red Heat Exchanger MaintenanceBurner Removal Instructions (Refer to FIGURES 12A and 12B)

Seite 15 - WARNING: Wearing

Form O-MAPS II, P/N 209179 R7, Page 22

Seite 16

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 23Flame Sensor - Refer to FIGURE 12B and locate the ame sensors (one on each burner section). Disconnect th

Seite 17 - 

Form O-MAPS II, P/N 209179 R7, Page 249.0 Gas Heat Section Maintenance (cont'd)Gas ValvesCarefully remove external dirt accumulation from the val

Seite 18

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 25(continued)10.0 Electric Heat Section Maintenance - Models REDA and RECADANGER: Turn off the power locking

Seite 19

Form O-MAPS II, P/N 209179 R7, Page 2611.0 Troubleshooting (cont'd)General Refrigeration Circuit (cont'd)SYMPTOM POSSIBLE CAUSE REMEDYG. Hig

Seite 20 - Steps 1-13 (cont'd)

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 27Troubleshooting - Gas Heat Section and Optional Curb Duct FurnacePROBLEM PROBABLE CAUSE REMEDYVenter motor

Seite 21

Form O-MAPS II, P/N 209179 R7, Page 28Record installation information on the back of the installation manual, Form I-MAPS II.Keep ALL booklets for fu

Seite 22 - 9.0 Gas Heat

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 3There are warning labels on the unit and throughout this manual. For your safety, comply with a

Seite 23 - Venter Motor

Form O-MAPS II, P/N 209179 R7, Page 4WARNING: Turn off the power before performing all maintenance procedures (except to check refrigerant

Seite 24 - (Side View

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 5

Seite 25 - General Refrigeration Circuit

Form O-MAPS II, P/N 209179 R7, Page 6Inlet Air Filters Size, Type, and P/N 3.0 Filters Cross-Reference by Model/Size and Cabinet Size A, B, or CBeca

Seite 26 - System Circuit Board)

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 7FIGURE 2A - Removi

Seite 27

Form O-MAPS II, P/N 209179 R7, Page 8Condenser Coil ConnectionsCoils in the Cabinet (Evaporative Coils)1. Verify that the electrical power has been tu

Seite 28

Form RZ-NA O-MAPS II, P/N 209179 R7, Page 9CKT DFIGURE 3E - Three Single CircuitsDischargeDischargeDischargeLiquidLiquidLiquidCkt BTwinnedCkt DCkt AAi