Reznor UDAP Bedienungsanleitung Seite 16

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 20
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 15
Form P-UD, Page 16
CODE 142 - Vertical Louvers (Same as Option CD1) - UDAP/UDAS/UDBP/UDBS








Install and adjust vertical louvers to achieve desired airow pattern.
CODE 140 - High Altitude Pressure Switch Kit - Above 6000 ft/1830M Elevation
(Same as Option DJ20, DJ21) - Models UDAP, UDAS, UDBP, UDBS as listed
See pressure switch locations in illustrations on pages 4 and 5.
Accessories/Options
CODE 141 - Vent Cap - Models UDAP and UDBP
(Same as Option CC1)
Code Description 30 45 60 75 100 125 150 175 200 225 250 300 350 400
140A
Vent Cap for
standard UDAP and
UDBP
111848, 4” 111849, 5” 111850, 6”
140B
Vent Cap for UDAP-
CV (Model UDAP
with Option AV6 for
common venting)
111848, 4”
111849,
5”
-- -- -- -- -- -- -- -- --
Option DJ20 for
Model UDAP
installed as a
standard Power
Vented Fan-Type
Unit Heater
Model UDAP 30 45 60 75 100 125 150 175 200 225 250 300 350 400
Pkg P/N 197117 197118 197117 201162
High Altitude Switch P/N 197031 197032 197031 201160
Negative Pressure OFF
Setpoint “w.c.
0.35 0.45 0.35 1.0
Label color Purple Pink Purple Brown
Option DJ21
applies only to
Model UDAP-CV
with Option AV6
for Common
Venting
Model UDAP-CV 30 45 60 75 100
Pkg P/N 197119 197118 197120 197121
High Altitude Switch P/N 197029 197032 196362 196388
Negative Pressure OFF
Setpoint “w.c.
0.60 0.45 0.55 0.50
Label color Lt Blue Pink White Orange
Option DJ20 for
Model UDAS
Separated
Combustion Fan-
Type Unit Heater
Model UDAS 30 45 60 75 100 125 150 175 200 225 250 300 350 400
Pkg P/N 197119 197121 197205 197117 201162
High Altitude Switch P/N 197029 196388 197030 197031 201160
Differential Pressure
OFF Setpoint “w.c.
0.60 0.50 0.40 0.35 1.0
Label color Lt. Blue Orange Green Purple Brown
Option DJ20 for
Model UDBP
Power Vented
Blower-Type High
Static Unit Heater
Model UDBP 30 45 60 75 100 125 150 175 200 225 250 300 350 400
Pkg P/N 197117 197118 197117 201162
High Altitude Switch P/N 197031 197032 197031 201160
Negative Pressure OFF
Setpoint “w.c.
0.35 0.45 0.35 1.0
Label color Purple Pink Purple Brown
Option DJ20 for
Model UDBS
Separated
Combustion
Blower-Type High
Static Unit Heater
Model UDBS 30 45 60 75 100 125 150 175 200 225 250 300 350 400
Pkg P/N 197117 197118 202103 197118 197117 197205 197117 201162
High Altitude Switch P/N 197031 197032 196362 197032 197031 197030 197031 201160
Differential Pressure
OFF Setpoint “w.c.
0.35 0.45 0.55 0.45 0.35 0.40 0.35 1.0
Label color Purple Pink White Pink Purple Green Purple Brown
Size 30, 45 60, 75 100, 125
150, 175,
200
225, 250
300, 350,
400
Option Pkg P/N 197097 197098 197099 201199 201200 201201
Components
Louver Frame Top and
Bottom
(2) 197056 (2) 197189 (2) 197190
Louver Frame Sides (2)197057 (2)197058 (2)197059 (2)197186 (2)197187 (2)197188
Screws
(20) 195638, #8-18 x 3/8” long, AB point, slotted indented serrated hex
washer head
Louvers (5)196232 (5)196231 (5)196233 (8)196572 (8)196573 (8)195315
Compression Springs (5)195046 (5)195046 (5)195046 (8)195046 (8)195046 (8)195046
Seitenansicht 15
1 2 ... 11 12 13 14 15 16 17 18 19 20

Kommentare zu diesen Handbüchern

Keine Kommentare