Figure 2. Charging Chart for S4BD-060CB Series (5 Ton Units) - TXV Matches
200
220
240
260
280
300
320
340
360
380
400
420
440
460
480
500
520
540
560
580
600
75 80 85 90 95 100 105110 115 120 125 130
135
Liquid Temperature (F
o
)
Remove refrigerant when above the curve
Add refrigerant when below the curve
Suct.
Press.
OUTDOOR TEMPERATURE (°F)
70 75 80 85 90 95 100 105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
123 263 143
125
264 146
287 146
127 265 149
289 149
312 149
129
266 152
290 152
313 152
337 152
131 267 156
291 155
314 155
338 155
361 155
133 292 158
315 158
339 158
363 158
386 158
135 317 161
340 161
364 161
387 161
411 160
137 341 164
365 164
388 164
412 164
435 163
139 342 167 366 167
389 167
413 167
437 167
141 367 170 391 170
414 170
438 170
143 392 173 415 173
439 173
145 417 176 440 176
147 441 178
149
Table 5. Charging Table for S4BD-060CB Series (5 Ton Units) - Orifice Matches
LEGEND
Shaded boxes indicate flooded conditions.
Rated design values. The suction pressure will be lower than design value if outdoor air flow, entering
dry bulb, or entering wet bulb temperatures are lower than design.
NOTES:
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures GREATER than charted values indicate an UNDERCHARGED system.
3. Discharge temperatures LESS than charted values indicate an OVERCHARGED system.