9
Suct.
Press.
OUTDOOR TEMPERATURE (°F)
70 75 80 85 90 95 100 105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
131 264 143
133
265 146
290 145
135 267 149
292 148
317 147
137
268 153
293 151
318 149
343 148
139 269 156
294 154
319 152
344 151
369 150
141 295 157
320 155
345 154
370 153
395 151
143 322 158
347 157
372 156
397 154
422 153
145 348 160
373 158
398 157
423 156
448 154
147 349 163 374 161
399 160
424 159
449 157
149 376 164 401 163
425 162
450 161
151 402 165 427 164
452 163
153 428 167 453 166
155 454 168
157
Table 3. Charging Table for S4BD-036 Series (3 Ton Units) - Orifice Matches
Table 4. Charging Table for S4BD-048 Series (4 Ton Units) - Orifice Matches
Suct.
Press.
OUTDOOR TEMPERATURE (°F)
70 75 80 85 90 95 100 105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
124 260 132
126
261 136
284 136
128 262 139
285 139
308 139
130
263 142
286 142
309 142
332 142
132 264 145
287 145
310 146
333 146
356 145
134 288 148
311 149
334 149
357 149
380 149
136 312 152
335 152
358 152
381 152
404 152
138 336 155
359 155
382 155
405 155
428 155
140 337 158 360 158
383 158
406 159
429 159
142 361 161 384 161
407 162
430 162
144 385 164 408 164
431 165
146 409 167 432 168
148 433 170
150
LEGEND
Shaded boxes indicate flooded conditions.
Rated design values. The suction pressure will be lower than design value if outdoor air flow, entering
dry bulb, or entering wet bulb temperatures are lower than design.
NOTES:
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures GREATER than charted values indicate an UNDERCHARGED system.
3. Discharge temperatures LESS than charted values indicate an OVERCHARGED system.