Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 27
Optional High Gas
Pressure Switch
Optional Low
Gas Pressure
Switch
Dual, Single-Stage Gas Valve
Ball Valve
Transducer
From Gas
Supply
To
Burner
Manifold Pressure Tap
Ball Valve
Actuator
FIGURE 15C -
Components in the
Heat Section Gas
Train - MAPS
®
III&IV
Cabinet C (Heat
Section Sizes 400,
500, 600, 700)
Single-Stage Operating Gas Valve - All gas trains have either a single-stage or a dual single-stage safety gas valve.
The gas valve must be checked annually to ensure that it is shutting off gas ow completely; follow the instructions in
box below.
Instructions:
1. Locate the 1/8" NPT pressure tap or taps on the
combination valve.
2. Turn the knob(s) or switch to the OFF position to
prevent ow to the manifold. Connect a manometer to
each of the 1/8” outlet pressure taps (1 on the single-
stage valve; 2 on the dual single-stage valve). NOTE:
Manometers (uid-lled gauges) with inches water
column scale are recommended. Turn the heater off.
On the valve, turn the knob(s) or switch to the ON
position.
3. Use nger(s) to fully block the burner orice(s).
Continue blocking for several seconds and observe
the manometers. If any pressure is indicated, the gas
valve is leaking. A leaking gas valve must be replaced
before the heater is put back in operation.
Orifice
Adapter
Orifice Adapter
Optional High Gas
Pressure Switch
Transducer
Ball
Valve
Single-Stage
Gas Valve
Ball Valve
Actuator
Optional Low Gas
Pressure Switch
Manifold Pressure Tap
FIGURE 15B -
Components in the
Heat Section Gas
Train - MAPS
®
III&IV
Cabinet B (Heat
Section Sizes 250
and 300)
FIGURE 16A - Top View of Single-Stage Gas
Valves used on Cabinet A or B Sizes
1/8” Outlet
Pressure
Tap
1/8” Outlet
Pressure
Tap
FIGURE 16B - Top View of Dual Single-Stage
Gas Valve used on Cabinet C Heat Section
1/8” Output
Pressure Tap
Inlet
Pressure Tap
Adjust Outlet
Pressure
Modulating Valve
The gas train also has a ball valve with an actuator to control gas ow. The ball valve
and actuator are located downstream of the regular or dual single-stage valve as
shown in FIGURE 17A.
Carefully clean external dirt accumulation from the actuator.
Pressure
Adjustment
Pressure
Adjustment
1/8”
Output
Pressure
Tap
Inlet Pressure
Tap
Adjust Outlet
Pressure