Form O-MAPSIII&IV Cabinets A/B/C, P/N 257004R8, Page 7
Filter
Clamp
Filter
Filter
Wing Screw,
P/N 205707,
and Retainer,
P/N 205709
(2 each)
Filter
Filter
FIGURE 2A -
Removing Filters
from Outside
Air Hood
1" Permanent
Aluminum Filters
for Outside Air
Hood are listed by
Cabinet Size A, B, or C
(see cross-reference, page 6)
*A - (4) 16 x 20, P/N 101607
*B - (4) 16 x 25, P/N 101609
C - (3) 16 x 25, P/N 101609;
(6) 16 x 20, P/N 101607
Cabinet Sizes A and B with Option AS16
Outside Air Hood
(Does not apply if
system includes
Option PE
power exhaust;
see below.)
Filter Clamps attach
with Wing Screws
P/N 205707
Filter
16x20x1
Filter
16x20x1
Filter
16x20x1
Filter
16x25x1
Filter
16x25x1
Filter
16x25x1
Filter
16x20x1
Filter
16x20x1
Filter
16x20x1
Inlet View
All Cabinet Size C with
either Outside Air Hood
Option AS16 or AS19
Instructions: Remove lters by loosening the wing screws and sliding the lter
clamp(s). Clean with soap and water, allow to dry, and replace. If it is more convenient
to keep an extra clean set of lters, quantities, lter sizes, and part numbers are listed.
* Apply only to Cabinet
Size A and B with outside
air hood Option AS16
.
FIGURE 2B - Removing Filters from Option AS19 Outside Air
Hood Installed on a Cabinet Size A or B with power exhaust
Option PE1 or PE2
Instructions: 1) Remove the four screws as illustrated. Lower the tray.; 2) Pull out
lters. Clean with soap and water. Allow to dry.; 3) Slide clean dry lters into tray.;
4) Re-position tray and replace screws.
1" Aluminum Filters: **A - (4) 18 x 20, P/N 194903; **B - (4) 20 x 25, P/N 101610
** Apply only to Cabinet Size A and B with outside air hood Option AS19.
Permanent Filters in
the Outside Air Hood
If equipped with an outside air hood, there are 1" permanent, aluminum lters at the
entrance of the hood. The lters act as a moisture eliminator and bird screen. See FIG-
URE 2A or 2B. When inspecting the inlet air lters, inspect the outside air hood lters.
If cleaning is needed, remove the lters, clean, rinse, dry and re-install.
Filters in an Optional
Energy Recovery
Module
If equipped with an energy recovery module (Option ER1A, ER1B, or ER1C), check
both inlet and exhaust lters. Replace as needed.
Cabinet
Size *
Inlet Air Filters (Merv 8) Exhaust Air Filters (Merv 8)
Filter Type & Size Qty P/N Filter Type & Size Qty P/N
A Pleated 20x25x2 2 104113 Pleated 20x25x2 2 104113
B
Pleated 16x25x2 2 104112 Pleated 16x25x2 2 104112
Pleated 12x25x2 2 114320 Pleated 12x25x2 2 114320
C
Pleated 16x25x2 2 104112 Pleated 16x25x2 2 104112
Pleated 20x25x2 2 104113 Pleated 20x25x2 2 104113
Pleated 16x16x2 1 104109 Pleated 16x16x2 1 104109
Pleated 16x20x2 1 104110 Pleated 16x20x2 1 104110
*See cross-reference of
MAPS
®
Models by Cabinet
Size A, B, or C on page 6.
3.2 Drive
Components
CAUTION: If the
blower is unused
for more than three
months, bearings
with a grease tting
should be purged
with new grease
prior to startup.
Setscrews - Check all of the setscrews (bearing/blower hubs and pulleys). Torque pul-
ley setscrews a minimum of 110 in-lb to 130 in-lb maximum.
A bearing hub setscrew for a 1-3/8" to 1-3/4" shaft requires a 5/16" socket and a tight-
ening torque of 165 in-lbs.
Belts - Check belt for proper tension and wear. If needed, follow instructions to adjust
belt tension. Replace worn belts.
Bearings - Bearings with a grease tting should be lubricated twice a year with a high
temperature, moisture-resistant grease. (Type NLGI-1 or -2 standard grease is recom-
mended.) Be sure to clean the grease tting before adding grease. Add grease with a
handgun until a slight bead of grease forms at the seal. Be careful not to unseat the
seal by over lubricating. NOTE: If unusual environmental conditions exist (tempera-
tures below 32°F or above 200°F; moisture; or contaminants), more frequent lubrica-
tion is required.
NOTE: If it is more convenient to keep an extra clean set of lters, lter sizes and part numbers are shown in the illustration.